Watts, Amps and Volts Calculator
Choose a direct current, single phase or three phase circuit, choose whether to find the amps, the watts or the volts, and enter the other two values and the power factor. You get the result along with the real power in watts, kilowatts or megawatts, the apparent power in volt-amperes, the reactive power and, for three phase, the line to neutral voltage. Everything runs in your browser.
For a direct current circuit, power in watts is volts times amps, so 12 V at 8.33 A is 100 W. For a single phase alternating current circuit, the real power is volts times amps times the power factor, P = V x I x pf. For a balanced three phase circuit, it is P = the square root of 3 x V x I x pf, where V is the line to line voltage, the one between two of the three wires, and the line to neutral voltage is that divided by the square root of 3, so 400 V line to line is about 231 V line to neutral. For example, 5 kW at 230 V single phase with a power factor of 1 draws 21.74 A, and a three phase load of 10 A at 400 V with a power factor of 0.8 uses 5.54 kW. The power factor is the share of the apparent power, in volt-amperes, that does real work, so a low power factor means more current for the same watts. Resistive loads such as heaters have a power factor of 1, and motors and other inductive loads have a lower one. Pick what you want to find, enter the other two values, and the tool also gives the apparent and reactive power. It does not size cables or breakers, so check the rules for your installation. Everything runs in your browser.
Related Tools
[6 suggestions]Ohm's Law Calculator: Voltage, Current, Resistance and Power
Enter any two of voltage, current, resistance and power to get the other two with Ohm's law, and add resistors in series or in parallel.
Student ToolsElectricity Cost Calculator: What an Appliance Costs to Run
Calculate the kWh and the cost of running any appliance per hour, day, week, month and year from its watts, the hours of use and the price of a kWh.
Math & MoneyWire Gauge Calculator: AWG Diameter, Resistance and Voltage Drop
Look up the diameter, cross-section and resistance of any AWG wire from 0000 to 40, and work out the voltage drop of a run of copper wire and the thinnest gauge for a drop limit.
Student ToolsLED Resistor Calculator: Series Resistor for an LED or Several LEDs
Find the series resistor for an LED from the supply voltage, the LED forward voltage and the current, with the standard value, the real current and the heat.
Student ToolsVoltage Divider Calculator: Output Voltage and Resistor Values
Find the output of a resistor voltage divider, with the effect of a load, or find the second resistor for the output you want, with the closest standard value.
Student ToolsEV Charging Calculator: Time, Energy, Cost and Range Added
Work out how long an electric car takes to charge, the energy from the wall, the cost and the distance added, from the battery size and the charger power.
Math & MoneyAbout the Watts, Amps and Volts Calculator
For a direct current circuit the power in watts is volts times amps, P = V x I, so 12 V at 8.33 A is 100 W. For a single phase alternating current circuit the real power also depends on the power factor, P = V x I x pf, so 230 V and 10 A at 0.8 is 1,840 W. For a balanced three phase circuit, P = sqrt(3) x V x I x pf, where V is the line to line voltage, the voltage between two of the three wires, and the line to neutral voltage is that divided by sqrt(3), so a 400 V supply is 230.94 V line to neutral. Wikipedia gives the same relation. With that, 5 kW at 230 V single phase and a power factor of 1 draws 21.739 A, which is the default, and a three phase load of 10 A at 400 V and 0.8 uses 5.543 kW, which is 6.928 kVA of apparent power. The apparent power is the real power divided by the power factor, in volt-amperes, and the reactive power is the square root of the apparent power squared minus the real power squared. A low power factor means more current for the same real power. The power factor must be above 0 and at most 1, and it is ignored for direct current. The tool does not choose a cable or a breaker, which depends on the length, the installation and the local rules, so use it for the arithmetic and check the standards for the rest.
How do I convert watts to amps?▾
Divide the watts by the volts, and for AC also by the power factor: I = P / (V x pf). For 5,000 W at 230 V and a power factor of 1, that is 21.74 A. For three phase, divide by sqrt(3) x V x pf as well.
How do I convert amps to watts?▾
Multiply amps by volts, and by the power factor for AC: P = V x I x pf. 10 A at 230 V and 0.8 is 1,840 W. For three phase use sqrt(3) x V x I x pf with the line to line voltage.
What is the power factor?▾
It is the share of the apparent power, in volt-amperes, that does real work, a number from 0 to 1. A heater is close to 1. Motors and other inductive loads have a lower one, and a lower power factor means more current for the same watts.
Which voltage do I use for three phase?▾
The line to line voltage, the one between two of the three wires, such as 400 V. The voltage from a line to neutral is that divided by sqrt(3), which is about 230 V for a 400 V system.
Can I use this to size a cable or breaker?▾
No. It gives the current from the power and the voltage, but the cable and breaker depend on the length, the way it is installed, the temperature and the rules in your area. Ask a qualified electrician for that.